Question 1

A vendor proposes three 400 kW UPS modules to support a planned critical load of 780 kW, describing the arrangement as N+1 redundant. The single-line diagram shows all three modules feeding one output switchboard, from which a single distribution path serves the data hall. What is the correct assessment of this design?

Show answer & explanation

Correct answer: D - Capacity redundancy only; the single distribution path remains a single point of failure

Question 2

A facility is built with two fully independent 2N power trains, each with its own UPS, batteries and distribution. Both trains are installed in the same plant room, within a single fire compartment. With respect to fault tolerance, what is the PRIMARY deficiency of this arrangement?

Show answer & explanation

Correct answer: C - A single event in the shared compartment can disable both trains at once

Domain 2: Management of Documentary Credits

Question 3

A cabinet dissipates 6 kW of heat and the installed equipment has a temperature rise (ΔT) of 10 K across it. Approximately what volume of air must be delivered to the cabinet intake to remove this heat?

Show answer & explanation

Correct answer: C - Approximately 1,790 m³/h

Question 4

A supplier offers a UPS rated 300 kVA / 240 kW to support a planned IT load of 260 kW, stating that the unit has ample headroom because the load is comfortably below 300 kVA. What is the correct assessment of this offer?

Show answer & explanation

Correct answer: A - The unit is undersized; its 240 kW real power rating is below the 260 kW load

Question 5

A data hall shows a return-to-supply temperature difference at the CRAH units of only 4 K, against a design equipment ΔT of 12 K. Installed cooling capacity comfortably exceeds the IT load, and no cabinet is reporting an elevated inlet temperature. Which condition is MOST likely present?

Show answer & explanation

Correct answer: B - Conditioned air is bypassing the IT equipment and returning directly to the units

Question 6

An engineer is calculating the agent quantity for a clean agent suppression system protecting a data hall. The hall has a 600 mm raised floor void and a suspended ceiling void, both of which fall inside the protected zone. Which volume must be used in the calculation?

Show answer & explanation

Correct answer: A - The room volume plus the raised floor void and the suspended ceiling void

Question 7

A three-phase distribution board supplies a balanced load at 400 V phase-to-phase. The measured line current is 100 A and the power factor is 0.9. What is the approximate real power being delivered?

Show answer & explanation

Correct answer: B - 62.4 kW

Question 8

An organisation is comparing Top-of-Rack (ToR) and End-of-Row (EoR) switching architectures for a new data hall. What is the PRINCIPAL disadvantage of the ToR approach?

Show answer & explanation

Correct answer: D - It significantly increases the number of switches that must be managed and maintained

Question 9

A facility maintains 24 °C (75.2 °F) measured at the return air inlet of every CRAH unit and claims compliance with the ASHRAE recommended thermal envelope. Which objection to this claim is valid?

Show answer & explanation

Correct answer: A - The envelope applies at the IT equipment air inlet, not at the unit return

More CDCS practice questions

Question 10

A 25-year-old data centre is scheduled to have its raised access floor tiles lifted and replaced while the facility remains live. Which specific contamination risk must be assessed and controlled before the work begins?

Show answer & explanation

Correct answer: D - Release of zinc whiskers from electroplated components in the floor understructure